Journal of Shanghai Jiaotong University
• Engineering Mechanics • Previous Articles Next Articles
CHENG Yulong,WU Yuyuan,WU Tiehui,LIU Kewei
Received:
Revised:
Online:
Published:
Abstract: It was shown by previous researches that the system of ammoniawaterlithium bromide absorption refrigerator, without solution heat exchanger and solution pump had a better thermal performance, a lower initial investment and a higher safety, compared with the previous patterns. For further improvement of the system, three novel systems with solution heat exchanger were proposed and designed. The experiments were also performed for these novel systems. When wNH3=50%, wLiBr=15%, the coefficient of the performance (COP) of systemⅠwas improved by 27.8%, and that of systemⅡwas improved by 65%, compared with the system without solution heat exchanger. By means of the solution heat exchanger, the COP was increased greatly. Finally, the defects of systemⅡwere discussed and further improved systemⅢ was presented.
CLC Number:
TB651
CHENG Yulong,WU Yuyuan,WU Tiehui,LIU Kewei . Experimental Research on the Ternary Solution Absorption Refrigerator with the Solution Heat Exchanger[J]. Journal of Shanghai Jiaotong University.