Temperature Control Scheme for Gas Turbine of Combined Cycles with Exhaust Gas Recirculation

LI Keying1,2, CHEN Kun1, JIANG Zepeng1, LI Chao1, GUO Xiaoguo1, ZHANG Shijie1,2()   

  1. 1. Institute of Engineering Thermophysics, Chinese Academy of Sciences, Beijing 100190, China
    2. School of Engineering Science,University of Chinese Academy of Sciences, Beijing 100049, China
  • Received:2023-04-11 Revised:2023-06-09 Accepted:2023-06-12 Online:2024-08-28 Published:2024-08-27

Abstract:

Under partial-load conditions, the combined application of exhaust gas recirculation of heat recovery steam generator and compressor inlet guide vane adjustment (EGR-IGVC) can effectively improve the performance of gas turbine combined cycle. However, if this strategy is combined with the temperature control scheme of constant T3(turbine inlet temperature)-T4m(maximum allowable turbine exhaust temperature), which is often adopted in gas turbine combined cycles under part-load conditions, it would cause a large bottoming cycle exergy destruction and a significant decrease in bottoming cycle power output at relatively lower loads. In this paper, a constant T3-T4m-T4d (the design value of turbine exhaust temperature) scheme suitable for the EGR-IGVC strategy is proposed, the PG9351FA gas turbine combined cycle unit is taken as the research object, and the partial-load performance of combined cycle under the two temperature control schemes is compared and investigated based on energy and exergy analysis. The results show that the combination of the EGR-IGVC strategy with the constant T3-T4m scheme is still the best at the ambient temperature of 15 ℃ and the partial-load rate of above 80%. At a load of 30%—80%, compared with the constant T3-T4m scheme, the EGR-IGVC strategy combined with the constant T3-T4m-T4d scheme can increase the gas turbine efficiency by 0.15%—0.47%, and decrease the exergy destruction of the heat recovery steam generator by more than 0.51%(2.15 MW). The results also show that adopting the constant T3-T4m-T4d scheme can always obtain higher combined cycle efficiency when the ambient temperature varies between 0 and 40 ℃. In addition, the increase in partial-load efficiency becomes more evident with the rise of ambient temperature.

Key words: gas turbine combined cycle, exhaust gas recirculation (EGR), compressor inlet guide vane (IGV), energy and exergy analysis, partial load