An Active Voltage-Reduction Arc- Suppression Method for 35 kV Distribution Networks with Phase-Source Feeding Considering Zero-Sequence Coupling of Main Transformer

Expand
  • 1. Electric Power Research Institute of Yunnan Power Grid Co., Ltd., Kunming 650217, China; 2. Lincang Power Supply Bureau of Yunnan Power Grid Co., Ltd., Lincang 677000, Yunnan, China; 3. State Key Laboratory of Disaster Prevention and Reduction for Power Grid, Changsha University of Science and Technology, Changsha 410114, China

Online published: 2026-10-01

Abstract

Single-phase-to-ground faults occur frequently in 35kV distribution networks, and the harm of arc overvoltage is severe, making it urgent to carry out neutral grounding mode transformation and active arc suppression. However, directly using the main transformer to derive the neutral point introduces zero-sequence magnetic coupling between the upper and lower power grids. The arc suppression regulation process can easily trigger cross-level zero-sequence current conduction, posing a risk of misoperation of the 110kV side protection. To address this issue, an active voltage-reduction arc suppression method fed by phase power supply considering the zero-sequence coupling of the main transformer is proposed. Firstly, a zero-sequence equivalent network considering the strong magnetic coupling between the 110kV and 35kV transformers is established to reveal the cross-level conduction mechanism of zero-sequence voltage and current under single-phase grounding faults and active arc suppression regulation. Secondly, a phase power supply reverse-feeding neutral point topology based on the Yyn6 transformer is proposed. By utilizing the inherent electromagnetic phase transformation characteristics of the transformer, the reverse potential of the faulted phase is fed into the 35kV neutral point, achieving rapid \"dual-zeroing\" of the fault phase voltage and residual current. Furthermore, the disturbance boundary of the active arc suppression process on the zero-sequence protection of the upper 110kV power grid is quantitatively defined. PSCAD/EMTDC multi-level grid simulation results show that the proposed method can clamp the fault phase voltage below 0.1kV and reduce the residual current below 0.1A, achieving reliable arc extinction. Meanwhile, throughout the fault and arc suppression processes, the zero-sequence current penetrating to the 110kV side remains far below the setting value of the main transformer zero-sequence protection, eliminating the risk of overstep tripping from both theoretical and simulation perspectives. The proposed method combines the high reliability of passive topology with the flexibility of active regulation, clearing theoretical obstacles and providing a new scheme for the economical grounding transformation and safe arc suppression of 35kV distribution networks.

Cite this article

YANG Jindong, SUN Zaizhao, LIAO Xiang, XIANG Yang . An Active Voltage-Reduction Arc- Suppression Method for 35 kV Distribution Networks with Phase-Source Feeding Considering Zero-Sequence Coupling of Main Transformer[J]. Journal of Shanghai Jiaotong University, 0 : 1 . DOI: 10.16183/j.cnki.jsjtu.2026.190

Outlines

/

〈 〉