Indoor temperature measurement of an enclosed gymnasium under membrane structure with natural ventilation was carried out during winter period. Air temperatures were measured from six positions with different heights and directions. Parameters relating to thermal environment were obtained, including indoor irradiation, velocity, globe temperature and relative humidity. This paper aimed to study indoor temperature distribution of the gymnasium and evaluate its thermal comfort by revised PMV-PPD index (aPMV-aPPD index). The results show that indoor irradiance is the main factor which effects the variation of indoor temperature. Mean air temperature inside was 3℃ higher than that outside. Air temperatures near the interior surface of the membrane roof kept higher in vertical direction and both amplitude and phase of the temperature decayed at positions in lower altitude. The aPMV value of the gymnasium inside ranged from -1.2 to -0.5 while aPPD varied from 15% to 40%. Without thermal insulation design in membrane structures, indoor environment in enclosed gymnasium hardly satisfies comfortable requirement under natural ventilation condition.
YIN Yue,HU Jianhui,CHEN Wujun,LI Yipo
. Indoor Thermal Environment Measurement of Enclosed Gymnasium with
Membrane Structure in Winter[J]. Journal of Shanghai Jiaotong University, 2018
, 52(11)
: 1452
-1458
.
DOI: 10.16183/j.cnki.jsjtu.2018.11.006
[1]HU J, CHEN W, CAI Q, et al. Structural behavior of the PV-ETFE cushion roof[J]. Thin-Walled Structures, 2016, 101: 169-180.
[2]HU J, CHEN W, ZHAO B, et al. Buildings with ETFE foils: A review on material properties, architectural performance and structural behavior[J]. Construction & Building Materials, 2017, 131: 411-422.
[3]陈务军.膜结构工程设计[M]. 北京: 中国建筑工业出版社, 2005: 51-55.
CHEN Wujun. Membrane structure engineering design[M]. Beijing: Chinese Construction Industry Press, 2005: 51-55.
[4]郭晓娟.膜结构建筑适用性分析[D].杭州: 浙江大学, 2013.
GUO Xiaojuan. Applicability analysis of membrane structure[D]. Hangzhou: Zhejiang University, 2013.
[5]ESCOFFIER A, ALBRECHT A, CONSIGNY F. Nice stadium: Design of a flat single layer ETFE roof[J]. International Journal of Structural and Construction Engineering, 2014, 8(3): 61-65.
[6]KUMAR A, SUMAN B M. Experimental evaluation of insulation materials for walls and roofs and their impact on indoor thermal comfort under composite climate[J]. Building and Environment, 2013, 59: 635-643.
[7]AFRIN S, CHILTON J, LAU B, et al. Evaluation and comparison of thermal environment of atria enclosed with ETFE foil cushion envelope[J]. Energy Procedia, 2015, 78: 477-482.
[8]HE J, HOYANO A. Measurement and evaluation of the summer microclimate in the semi-enclosed space under a membrane structure[J]. Building and Environment, 2010, 45(1): 230-242.
[9]陈钢.新形式创造新功能——上海交通大学体育馆建筑设计[J].城市建筑, 2008(11): 62-64.
CHEN Gang. New form creates new function—Design of the gymnasium in Shanghai Jiao Tong University[J]. Urbanism and Architecture, 2008(11): 62-64.
[10]VAN HOOFF T, BLOCKEN B. Full-scale measurements of indoor environmental conditions and natural ventilation in a large semi-enclosed stadium: Possibilities and limitations for CFD validation[J]. Journal of Wind Engineering and Industrial Aerodynamics, 2012, 104/105/106: 330-341.
[11]中国气象局. 风力等级: GB/T 28591—2012 [S].北京: 中国标准出版社, 2012: 1-2.
China Meteorological Administration. Wind Scale: GB/T 28591—2012 [S]. Beijing: Standards Press of China, 2012: 1-2.
[12]HOLMAN J P. Heat transfer, tenth edition[M]. New York: Mc Graw-Hill, 2010: 139-145.
[13]FANGER P O, TOFTUM J. Extension of the PMV model to non-air-conditioned buildings in warm climates[J]. Energy & Buildings, 2002, 34(6): 533-536.
[14]YAO R M, LI B Z, LIU J. A theoretical adaptive model of thermal comfort—Adaptive Predicted MeanVote (aPMV)[J]. Building & Environment, 2009, 44(10): 2089-2096.
[15]中华人民共和国住房与城乡建设部. 民用建筑室内热湿环境评价标准: GB/T 50785—2012 [S]. 北京: 中国建筑工业出版社, 2012: 17-21.
Ministry of Housing and Urban-Rural Development of the People’s Republic of China. Evaluation standard for indoor thermal environment in civil buildings: GB/T 50785—2012 [S]. Beijing: Standards Press of China, 2012: 17-21.
[16]International Orgarization for Standardization. ISO 7726-2001. Ergonomics of the thermal environment-Instruments for measuring physical quantities [S]. Geneva: International Organization for Standardization, 2001: 7-49.
[17]ASHRAE. ANSI/ASHRAE Standard 55-2010: Thermal Environment Conditions for Human Occupancy [S]. Atlanta: American Society of Heating Ventilating and Air-Conditioning Engineers, 2011: 4-11.