Journal of Shanghai Jiao Tong University ›› 2026, Vol. 60 ›› Issue (7): 1141-1150.doi: 10.16183/j.cnki.jsjtu.2024.381

• New Type Power System and the Integrated Energy • Previous Articles     Next Articles

Single-Phase-to-Ground Fault Protection on Valve Side of Hybrid Modular Multilevel Converters Based on Thyristor-Branch-Loop

LIN Jinjiao1, ZHU Zijian2, ZHENG Junchao1, TAO Yan1, DENG Fujin2()   

  1. 1 Electric Power Research Institute of State Grid Jiangsu Electric Power Co., Ltd., Nanjing 211103, China
    2 School of Electrical Engineering, Southeast University, Nanjing 210096, China
  • Received:2024-09-26 Revised:2024-10-26 Accepted:2025-01-16 Online:2026-07-28 Published:2026-08-05
  • Contact: DENG Fujin E-mail:fdeng@seu.edu.cn

Abstract:

In high voltage direct current (HVDC) systems based on modular multilevel converters (MMCs), single phase to ground (SPG) fault on the MMC valve side may lead to serious consequences such as overvoltage damage to the submodules of MMC bridge arms, and affect system reliability. Therefore, this paper analyzes the characteristics of SPG faults on the valve side of traditional hybrid MMC based HVDC systems, and proposes a hybrid MMC topology based on a thyristor-branch-loop for value-side SPG fault protection of the HVDC system. In the proposed topology, each arm consists of full bridge and half bridge submodules, while the thyristor branch connects the three-phase lower-arm inductors to form a loop. In the case of SPG fault, the proposed hybrid MMC can suppress the lower-arm current, clamp the alternating current voltage on the MMC valve side, and interrupt the MMC fault current through the thyristor-branch-loop and blocking submodules. The proposed topology features low overvoltage, short current self-shutdown time, fewer full bridge submodules, and low power consumption. The effectiveness of the proposed topology and control strategy is verified by PSCAD/EMTDC simulation and experiments.

Key words: high voltage direct current (HVDC) system, modular multilevel converter (MMC), single phase to ground (SPG) fault on the valve side, thyristor-branch-loop