Journal of Shanghai Jiaotong University ›› 2016, Vol. 50 ›› Issue (04): 540-544.

Previous Articles     Next Articles

Optimization of IGV Temperature Control Strategy for Gas Turbine Considering Ambient Temperature and Load

CHEN Jinwei,CHEN Meishan,MEI Jiaojiao,ZHANG Huisheng   

  1. (Gas Turbine Research Institute, Shanghai Jiaotong University, Shanghai 200240, China)
  • Received:2015-03-05 Online:2016-04-28 Published:2016-04-28

Abstract: Abstract: In view of the importance of exhaust temperature of gas turbine to the operation of a power unit under offdesign condition, the function and principles of temperature control of inlet guide vane (IGV) were introduced by taking the gas turbine of a combine cycle as a study object. With the conditions of load and ambient temperature changed, the dynamic response process of thermodynamic parameters of gas turbine was compared and analyzed under three different control strategies, ie., pure feedback control, feedforwardfeedback control and double feedforwardfeedback control. The results show that the control characteristic of double feedforwardfeedback control strategy is better than that of other control strategies.

Key words: Key words: gas turbine, inlet guide vane(IGV); temperature control, feedforward control, feedback control