基于时-频行波全息映射的有源配电网故障定位方法
曾举鹏, 曾祥君, 白浩, 喻锟, 杨炜晨, 龙璇林, 壮婕

Fault Location Method for Active Distribution Networks Based on Holographic-Mapping of Time-Frequency Traveling Waves
ZENG Jupeng, ZENG Xiangjun, BAI Hao, YU Kun, YANG Weichen, LONG Xuanlin, ZHUANG Jie
表4 不同故障初相角下定位结果
Tab.4 Simulation results of different fault initial angles
故障初相角/(°) [ V ( p ) ,   T a n i ( S F ,   S V ( p ) ) ] [ V ( p + 1 ) ,   T a n i ( S F ,   S V ( p + 1 ) ) ] 故障区段 定位结果(参考端)/km 定位误差/m
1.5 [V(32), 0.9376] [V(33), 0.9811] E8E9 2.8891(E8) 10.9
5 [V(32), 0.9424] [V(33), 0.9903] E8E9 2.8658(E8) 34.2
30 [V(32), 0.9464] [V(33), 0.9986] E8E9 2.8665(E8) 33.5
60 [V(32), 0.9465] [V(33), 0.9986] E8E9 2.8780(E8) 22.0
90 [V(32), 0.9460] [V(33), 0.9985] E8E9 2.8747(E8) 25.3