基于时-频行波全息映射的有源配电网故障定位方法
|
|
曾举鹏, 曾祥君, 白浩, 喻锟, 杨炜晨, 龙璇林, 壮婕
|
Fault Location Method for Active Distribution Networks Based on Holographic-Mapping of Time-Frequency Traveling Waves
|
|
ZENG Jupeng, ZENG Xiangjun, BAI Hao, YU Kun, YANG Weichen, LONG Xuanlin, ZHUANG Jie
|
|
表3 不同过渡电阻下定位结果
|
Tab.3 Simulation results of different fault resistances
|
|
| 过渡电阻/Ω | | | 故障区段 | 定位结果(参考端)/km | 定位误差/m | | 0 | [V(17), 0.9412] | [V(18), 0.9997] | E1E6 | 0.0152(E6) | 15.2 | | 50 | [V(17), 0.9410] | [V(18), 0.9998] | E1E6 | 0.0105(E6) | 10.5 | | 500 | [V(17), 0.9413] | [V(18), 0.9997] | E1E6 | 0.0077(E6) | 7.7 | | 1 000 | [V(17), 0.9413] | [V(18), 0.9995] | E1E6 | 0.0081(E6) | 8.1 | | 5 000 | [V(17), 0.9395] | [V(18), 0.9987] | E1E6 | 0.0128(E6) | 12.8 |
|
|
|