基于时-频行波全息映射的有源配电网故障定位方法
曾举鹏, 曾祥君, 白浩, 喻锟, 杨炜晨, 龙璇林, 壮婕

Fault Location Method for Active Distribution Networks Based on Holographic-Mapping of Time-Frequency Traveling Waves
ZENG Jupeng, ZENG Xiangjun, BAI Hao, YU Kun, YANG Weichen, LONG Xuanlin, ZHUANG Jie
表2 不同故障类型下定位结果
Tab.2 Simulation results of different fault types
故障类型 [ V ( p ) ,   T a n i ( S F ,   S V ( p ) ) ] [ V ( p + 1 ) ,   T a n i ( S F ,   S V ( p + 1 ) ) ] 故障区段 定位结果(参考端)/km 定位误差/m
AG [V(1), 0.9877] [V(2), 0.9502] E1E2 1.3296(E1) 29.6
CG [V(1), 0.9878] [V(2), 0.9502] E1E2 1.3255(E1) 25.5
AB [V(1), 0.9877] [V(2), 0.9502] E1E2 1.3140(E1) 14.0
BCG [V(1), 0.9880] [V(2), 0.9503] E1E2 1.3201(E1) 20.1
ABC [V(1), 0.9878] [V(2), 0.9500] E1E2 1.3099(E1) 9.9