The setting of parameters of signal quality bit will cause the failure on demand or spurious failure of digital control system(DCS) in nuclear power plant. To solve this problem, limitations of general scheme based on the current design status are analyzed. A new design method is proposed. The function of DCS is confirmed by the status of nuclear power plant. It not only solves the problems caused by quality bit setting, but also simplifies the operator’s operation to a certain extent. It improves the safety and availability of the nuclear power plant and promotes intelligence and unmanned developments in the nuclear power plant. Thermal physical parameters in the steady state and manual operation in the process of state transition are used to identify the state of the nuclear power plant. It helps DCS to perform expected functions. And it can avoid the occurrence of unexpected events.
XIAO Peng,LIU Hongchun,JIAN Yifan,ZHAO Yang,LI Wei,TANG Tao
. Consideration on the Setting of Signal Quality Bit in
the DCS of Nuclear Power Plant[J]. Journal of Shanghai Jiaotong University, 2019
, 53(Sup.1)
: 12
-16
.
DOI: 10.16183/j.cnki.jsjtu.2019.S1.003
[1]管运全, 徐霞军, 王琪, 等. 田湾核电站安全仪控系统运行及维护经验[J]. 核电子学与探测技术, 2013, 33(3): 345-348.
GUAN Yunquan, XU Xiajun, WANG Qi, et al. Tianwan NPP safety I & C system operation and maintenance experience[J]. Nuclear Electronics & Detection Technology, 2013, 33(3): 345-348.
[2]黄甦. 基于TXS/T2000核电厂DCS信号失效下质量位设置[J]. 核安全, 2019, 18(5): 38-42.
HUANG Su. Research of quality bits setting for DCS signal fault in nuclear power plant based on TXS/T2000[J]. Nuclear Safety, 2019, 18(5): 38-42.