考虑植被碳化机理的配电网触树弧光接地故障建模

展开
  • 1. 长沙理工大学电网防灾减灾全国重点实验室,长沙 410114; 2. 中国能源建设集团广东省电力设计研究院有限公司, 广州 510663
邓清波(1999—),博士生,从事电力系统保护与控制研究。
曾祥君,教授,博士生导师;E-mail:eexjzeng@qq.com。

网络出版日期: 2026-10-11

基金资助

国家自然科学基金(U22B20113,52477073)资助项目

Modeling Study on Tree-Contact Arc Grounding Faults in Distribution Networks Considering Vegetation Carbonization Mechanism

Expand
  • 1. State Key Laboratory of Disaster Prevention & Reduction for Power Grid, Changsha University of Science and Technology, Changsha 410114, China; 2. Guangdong Electric Power Design Institute Co., Ltd., China Energy Engineering Group, Guangzhou 510663, China

Online published: 2026-10-11

摘要

针对配电网触树接地故障下传统模型因忽略介质碳化与燃弧电压动态演变而导致的高阻阶段表征失真问题,基于 10 kV 配电网全尺寸物理真型试验,揭示了植被受热碳化过程中接地阻抗与介质绝缘强度的动态演化机理。提出了一种分段式植被碳化等效电阻模型,定量刻画了植被从初始接触至完全碳化全过程电阻率呈指数级衰减的演化规律;在此基础上,引入灰烬颗粒与气体密度修正系数,构建了计及击穿场强动态衰减的改进 Cassie 动态电弧模型,并串联耦合形成触树接地故障综合物理模型。在 PSCAD/EMTDC 仿真平台上对该模型进行了复现与验证,结果表明该模型能够准确复现故障电流的周期性包络上升与燃弧电压的平顶畸变等微观非线性特征,攻克了触树弧光接地故障全过程精准表征的难题,为配电网高阻故障仿真与感知保护算法研制提供了坚实的物理模型支撑。

本文引用格式

邓清波, 曾祥君, 喻锟, 曾超, 覃伊铭, 曾举鹏, 柴阳灏 . 考虑植被碳化机理的配电网触树弧光接地故障建模[J]. 上海交通大学学报, 0 : 1 . DOI: 10.16183/j.cnki.jsjtu.2026.131

Abstract

Traditional models cannot accurately characterize the high-resistance phase during tree-contact grounding faults in distribution networks because they neglect dielectric carbonation and dynamic arc voltage evolution. To resolve this distortion problem, the dynamic evolution mechanisms of grounding impedance and dielectric strength during vegetation thermal carbonation were revealed based on full-scale physical tests in a 10 kV distribution network. A piecewise vegetation carbonation equivalent resistance model was proposed. This model quantitatively characterizes the exponential decay of resistivity from initial contact to complete carbonation. Furthermore, an improved Cassie dynamic arc model considering dynamic breakdown field strength attenuation was constructed by introducing correction coefficients for ash particles and gas density. This arc model was then coupled in series with the carbonation resistance model to form a comprehensive physical model for tree-contact grounding faults. The proposed model was reproduced and validated on the PSCAD/EMTDC simulation platform. Experimental and simulation results show that the comprehensive model accurately reproduces microscopic non-linear features, including the periodic envelope growth of fault current and the flat-top distortion of arc voltage. This model overcomes the challenge of accurately characterizing the entire process of tree-contact high-resistance grounding faults. It provides a solid physical foundation for high-resistance fault simulation and sensing protection algorithms in distribution networks.
文章导航

/

〈 〉