35kV配电网单相接地故障频发且电弧过电压危害大,亟需开展中性点接地方式改造与主动消弧。然而,直接利用主变压器引出中性点会引入上下级电网的零序磁耦合,消弧调控过程极易引发跨级零序电流传导,存在导致110kV侧保护误动的风险。针对此问题,提出一种计及主变压器零序耦合的35kV配电网相电源馈入主动降压消弧方法。首先,建立计及110kV-35kV变压器强磁耦合的零序等值网络,揭示单相接地故障及主动消弧调控下零序电压与电流的跨级传导机理;其次,提出基于Yyn6型变压器的相电源反相馈入中性点拓扑,利用变压器固有的电磁相位变换特性,将故障相反相电势馈入35kV中性点,实现故障相电压与残流的快速“双归零”;进一步,定量界定了主动消弧过程对上级110kV电网零序保护的扰动边界。PSCAD/EMTDC多级电网仿真结果表明:该方法可将故障相电压钳制至0.1kV以下,残流降至0.1A以下,实现可靠熄弧;同时,在故障及消弧全过程中,向110kV侧渗透的零序电流均远低于主变零序保护整定值,从理论与仿真层面排除了越级跳闸风险。该方法兼具无源拓扑的高可靠性与主动调控的灵活性,为35kV配电网经济型接地改造与安全消弧扫清了理论障碍并提供了新方案。
Single-phase-to-ground faults occur frequently in 35kV distribution networks, and the harm of arc overvoltage is severe, making it urgent to carry out neutral grounding mode transformation and active arc suppression. However, directly using the main transformer to derive the neutral point introduces zero-sequence magnetic coupling between the upper and lower power grids. The arc suppression regulation process can easily trigger cross-level zero-sequence current conduction, posing a risk of misoperation of the 110kV side protection. To address this issue, an active voltage-reduction arc suppression method fed by phase power supply considering the zero-sequence coupling of the main transformer is proposed. Firstly, a zero-sequence equivalent network considering the strong magnetic coupling between the 110kV and 35kV transformers is established to reveal the cross-level conduction mechanism of zero-sequence voltage and current under single-phase grounding faults and active arc suppression regulation. Secondly, a phase power supply reverse-feeding neutral point topology based on the Yyn6 transformer is proposed. By utilizing the inherent electromagnetic phase transformation characteristics of the transformer, the reverse potential of the faulted phase is fed into the 35kV neutral point, achieving rapid \"dual-zeroing\" of the fault phase voltage and residual current. Furthermore, the disturbance boundary of the active arc suppression process on the zero-sequence protection of the upper 110kV power grid is quantitatively defined. PSCAD/EMTDC multi-level grid simulation results show that the proposed method can clamp the fault phase voltage below 0.1kV and reduce the residual current below 0.1A, achieving reliable arc extinction. Meanwhile, throughout the fault and arc suppression processes, the zero-sequence current penetrating to the 110kV side remains far below the setting value of the main transformer zero-sequence protection, eliminating the risk of overstep tripping from both theoretical and simulation perspectives. The proposed method combines the high reliability of passive topology with the flexibility of active regulation, clearing theoretical obstacles and providing a new scheme for the economical grounding transformation and safe arc suppression of 35kV distribution networks.